Extreme Networks WM-4T1i Especificações Página 69

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 306
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 68
Extreme Networks Consolidated Hardware Guide 2-25
Applicable Industry Standards
1 To find VA (Volt-Amps), locate the voltage and amperage requirements for each
piece of equipment. These numbers are usually located on a sticker on the back or
bottom of your equipment. Then multiply the numbers together to get VA:
VA = Volts x Amperes
2 Add the VA from each piece of equipment together to find the total VA requirement.
To determine the minimum amperage requirements for your UPS, we recommend
that you add 30% to the total.
UPS Transition Time
Transition time is the time that is necessary for the UPS to transfer from utility power to
full-load battery power. For Extreme Networks products, a transition time of less than
20 milliseconds is required for optimum performance.
Applicable Industry Standards
For more information, see the following ANSI/TIA/EIA standards:
ANSI/TIA/EIA-568-Adiscusses the six subsystems of a structured cabling system.
ANSI/TIA/EIA-569-Adiscusses design considerations.
ANSI/TIA/EIA-606discusses cabling system administration.
ANSI/TIA/EIA-607discusses commercial building grounding and bonding
requirements.
You can access these standards at http://www.ansi.org/ or http://www.tiaonline.org/.
Vista de página 68
1 2 ... 64 65 66 67 68 69 70 71 72 73 74 ... 305 306

Comentários a estes Manuais

Sem comentários